V-CELL FILTER
- Robust construction
- Long operating life
- Very large surface area
- Large surface area
- No metal parts
- Ideal for HVAC & Gas turbine
"HYGIENO" filters are manufacturing V-Cell filters to provide high efficiency filtration at low energy consumption and compact format. V-Cell can be used in any air conditioning application and preparatory filtration in cleanrooms.
Advantages
- Competitive cost effective 4V-Bank design filter with less than 100Pa
- Efficiency guarantee : No discharge effect, exceeding EN779:2011 performances' requirement
- Contains a very small fiber diameter material in a rigid and safe frame design. This guarantees very high and consistent filter efficiency for sub-micron particles.
- Reliable performance makes it the ideal final stage filter to meet the European standard for ventilation of non-residential buildings, EN13779.
Description
Application | Air conditioning applications and pre-filtration for clean room |
Type | High efficiency, incinerable filter. |
Frame | ABS. |
Media | Glass fiber paper. |
Separator | Hot-melt beads. |
Sealant | Polyurethane. |
EN779:2012 filter class | M6, F7, F8, F9. |
ASHRAE 52.2:1999 filter class | MERV 11, MERV 13, MERV 14, MERV 15. |
Recommended final pressure drop | 500 Pa |
Temperature | 70°C maximum in continuous service. |